Destratification Fans



CALECON - THERMAL ECONOMISER


THERMAL ECONOMISER THERMAL ECONOMISERDimensions










Model A B
  mm mm
CEC 1250 500 357
CEC 2250 600 357
CEC 3750 655 357
CEC 6500 805 357
It is a basic law of physics that hot air rises and in high roofed buildings this will cause a temperature gradient with hot air under the roof and cooler air at floor level. Calecon thermal economiser units will automatically recirculate high level hot air, reducing stratification and associated heat losses.

Specifications

MODEL
Max. Throw for Various Temp. Differentials
Air Flow
Motor
Amps
Wei-
ght
5°C
10°C
15°C
20°C
1 Phrase
3 Phrase
CEC
m
m
m
m
m3/s
watts
Start
Run
Start
Run
kg
1250
9
7
5.5
5
0.590
40
0.9
0.53
0.6
0.3
15.5
2250
12
8
7
6
1.062
100
1.65
0.87
1
0.5
21.0
3750
18
12
9
8
1.770
370
6.3
2.7
4.6
1.3
24.0
6500
24
15
13
10
3.067
370
6.3
2.7
4.6
1.3
35.0

Noise Levels

MODEL
LINEAR
CEC
dBA
63Hz
125Hz
250Hz
500Hz
1KHz
2KHz
4KHz
1250
52
53
64
55
51
48
45
40
2250
59
53
65
59
59
54
51
43
3750
68
65
69
69
65
63
60
53
6500
71
67
72
71
69
65
62
56
Sound lvl values at distance of 5 metres




| Heating Services inc. Hire Heat Services |
| Ray Lane Business Park, Kenlis Road, Barnacre, Preston, PR3 1GD. |
| TEL : 01995 601000 | FAX : 01995 600966 |